SGT-500PL

SGT-500PL

Engine : PERKINS
Alternator : Leroy Somer


Standby
500 kVA
Prime
450 kVA
Frequency
50
Voltage
400/231
Phase
3
Cos φ
0.8 kVA
SGT-500PL

Technical Features


Engine Specifications

Engine Brand
PERKINS
Engine Model
2506A-E15TAG1
Standby Power (Kw/hp)
451/604,8
Engine Speed (r.p.m)
1500
Total Displacement (L)
15.2
Cylinder Arrangement
6-L
Bore x Stroke (mm x mm)
137 x 171
Compretion Ratio
16:01
Governor Type
Electronic
Aspiration System
Turbocharged AAC
Injection
Direct
Cooling System
Water Cooled
Electrical System (VDC)
24
Oil Capacity (L)
62
Coolant Capacity (L)
58
Fuel Tank Capacity (L)
680
Maximum Exhaust Gas Temperature (°C)
550
Maximum Exhaust Gas Flow (m3/h)
4860
Maximum Back Pressure (kPa)
6.8
Cooling Air Flow (m3/min)
722
Fuel Consumption at 50 % (L/h)
50
Fuel Consumption at 75 % (L/h)
72
Fuel Consumption at 100 % (L/h)
95
Cylinder Liner Type
Wet Type-Replacable
Air Filter Type
Dry Type-Replacable
Radiator
Tropical type up to 50 °C

Alternator Specifications

Alternator Brand
Leroy Somer
Alternator Model
TAL0473 B
Frequency (Hz)
50
Nominal Power (kVA)
455
Nominal Voltage (V)
400
Phase
3
Regulated By
AVR
Voltage Regulation
± 0.8 %
Short Circuit Current
100% In
Insulation
Class H
IP Class
IP 23
Power Factor
0.8
Efficiency (%)
94.6
THD
< 1.5 %
Connection Type
Star connection
Number of Wires
6
Poles
4 pole
Bearing Type
Single Bearing

Open Type Dimensions and Weight

Width (mm)
1500
Length (mm)
3300
Height (mm)
2150
Weight (Kg)
3624
Fuel Tank Capacity (L)
680

Canopy Type Dimensions and Weight

Width (mm)
1500
Length (mm)
4600
Height (mm)
2904
Weight (Kg)
4324
Fuel Tank Capacity (L)
680